GRIPEDIA FIELD GUIDE β’ Electric, Power & Control β’ HOLLYWOOD, CALIFORNIA, USA
Cam-Lok 3-Phase Distribution, Balancing & Double-Neutral Harmonics
Strict Ground-Neutral-Hots hookup order, 120/208V Wye leg math ($P = β3 V I PF$), phase balancing under 10%, and triplen LED harmonic heating.
Direct Field Answer: Studio location power runs on 120V/208V 3-Phase 4-Wire Wye diesel generators fed by Series 16 single-pole Cam-Lok cables. Safe set electrical work obeys the Green β White β Black/Red/Blue make sequence (reverse on break), balances phase loads within 10%, and specifies Double-Neutral (2Γ 4/0 AWG White) cables to absorb additive triplen LED/HMI harmonics.
1. Series 16 Cam-Lok Color Sequence & Ampacity
| Hookup Step | Conductor | Jacket Color | Nominal Voltage | Standard 4/0 SC Ampacity | Break Order |
|---|---|---|---|---|---|
| 1st Connected | Equipment Ground | Green | 0 V Earth Reference | 400 A Continuous | Last Disconnected (5th) |
| 2nd Connected | Neutral (Double Return) | White | 0 V Star Point | 400 A / 800 A (2Γ 4/0) | 4th Disconnected |
| 3rd Connected | Phase A (L1) | Black | 120 V to N / 208 V L-L | 400 A | 1stβ3rd Disconnected |
| 4th Connected | Phase B (L2) | Red | 120 V to N / 208 V L-L | 400 A | 1stβ3rd Disconnected |
| 5th Connected | Phase C (L3) | Blue | 120 V to N / 208 V L-L | 400 A | 1stβ3rd Disconnected |
2. Diagram: Make-Before-Break Cam-Lok Sequence & 3-Phase Wye Star
3. Three-Phase Power Capacity & Practical Math
- Line Current Formula: $I_{\text{line}} = P_{\text{total}} / (\sqrt{3} \times 208\text{V} \times \text{PF}) \approx P_{\text{total}} / (360.26 \times \text{PF})$.
- 100 kW Genny Reality: At 0.95 power factor, maximum continuous output per leg equals roughly 292 A (not 400 A!). Leaving 20% headroom protects against sudden 18K HMI strike transients and neutral harmonic heating.
- 208V vs. 120V Circuits: Balanced 208V high-output ballasts draw across two hot Cam phases without pushing neutral return currentβsaving neutral copper capacity on LED stages.
Hardware Engineered for This Rigging Standard
Frequently Asked Set Questions
Q: What is the mandatory connection and disconnection order for Cam-Lok feeder cables?
Connect Green (Ground) first, White (Neutral) second, then Hot Phases Black, Red, and Blue last. When striking, reverse the exact order: disconnect all three Hots first, then White Neutral, then Green Ground last.
Q: Why do LED and HMI sets require double-neutral (200%) 4/0 feeder runs?
Non-linear switch-mode power supplies create 3rd-order triplen harmonics (180 Hz) that are in-phase across all three legs and add constructively in the neutral wire instead of canceling out, driving neutral amps past 130 to 170 percent of single-leg load.
Q: How close should A, B, and C phase currents remain on a 100kW tow-plant?
Keep phase leg amperage balanced within 10 percent across Black, Red, and Blue legs to prevent generator governor hunting, voltage sags, and harmonic overheating.
VERIFIED IN HOLLYWOOD, CALIFORNIA, USA β’ EST. 1962
Cam-Lok 3-Phase Distribution, Balancing & Double-Neutral Harmonics